Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country


Group: 1258
Part number 113434
Suitable for preventing condensation at pipe support locations of chilled-water and cold-water pipelines and as an insulation clamp for heating systems
Suitable for soundproof installation according to DIN 4109
Consisting of pipe clamp and insulation insert.
Max. temperature | 110 °C |
Min. temperature | 0 °C |
Thermal Conductivity λ {0°C} | λ ≤ 0,038 W/Mk |
Fire Performance | EL according to DIN EN 13501-1 |
Water vapour diffusion resistance factor | µ ≥ 7.000 |
Storage condition | In dry, clean rooms with humidity 50 - 70% and room temperature 0 - 35°C |
Material base body | steel |
Material insulation body | PUR |
Material connecting element | steel |
Surface | electro galvanized (Fe//Zn) |
Corossion class | C2 |
Certification

Enclose the insulation insert around the pipe, remove the protective paper strip on both sides of the insert and merge the longitudinal seam. Fix the pipe clamp in the centre of the plastic spacers. Lag the pipe insulation to each end of the insulation insert.
For horizontal installations to a wall-face, the plastic spacers on the insulation insert have to coincide with the pipe clamp flanges positioned over and under the pipe. Support distances see Installation Guidelines, chapter 'Pipe support'.