Group: 1260
Part number 804224
For high static requirements in plant constructions, design similar to DIN 3567
Holes for standard tensioning bolts and anchors without loss of load capacity

B1 | 391 mm |
b1 | 60 mm |
D | 291 mm |
D1 | 291 mm |
d | 17 mm |
e | 351 mm |
H | 307 mm |
t | 8 mm |
Two-piece pipe clamp delivered without bolts.
For suitable bolts, please see catalog.
-VZ,perm. | 42,00 kN |
Admissible load valid with fixation on both sides.
The max. permissible load capacity of the connected parts (e.g. anchors) shall be considered.
The max. adm. load capacity is determined by the application of statistical methods resulting from the breaking loads, under observance of a max. adm. deformation of 1.5 mm resp. 2% of the max. stretchable pipe dia.
Material base body | steel |
Surface | uncoated |
Corossion class | C2 |
Certification

Tightening torque and recommended clamping bolts:
| Size range [mm] | Recommended clamping bolts | Tightening torque [Nm] |
|---|---|---|
| 14 - 49 | M10 x 40 | 20 |
| 57 - 109 | M12 x 45 | 40 |
| 109 - 163 | M12 x 50 | 40 |
| 163 - 273 | M12 x 55 | 40 |
| 317 - 374 | M16 x 60 | 100 |
| 397 - 610 | M16 x 65 | 100 |