Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country



Group: 1382
Part number 190352
Fixed Point Chilled Water Clamp for absorption of axial forces, especially for risers
Contraction forces transferred to the pipe clamp via welded steel pressure ring
Clamp anchored to the building structure using an installed anchor bracket
4 half shells, 4 splice plates, 1 pressure ring as well as bolts and nuts.
Delivery time: 10 working days
VX,perm. | 9,00 kN |
Max. temperature | 105 °C |
Min. temperature | -50 °C |
Thermal Conductivity λ {0°C} | 0,042 W/mK |
Fire Performance | EL according to DIN EN 13501-1 |
Bulk Density | 250,00 kg/m³ |
Water vapour diffusion resistance factor | µ 1000 |
Material insulation body | PUR |
Material connecting element | steel |
Corossion class | C2 |
Delivery time: 10 business days
1. Weld pressure ring to pipe at location of required anchor point and conserve subsequently. Welding process, filler metal and dimensioning of the weld size are to be specified by the customer. For stainless steel pipes select a suitable welding filler (recommendation: 1.4370) to avoid contact corrosion.
2. Apply a thin bead of sealant to the inside adjacent shell faces of the clamp.
3. Position clamp shells on either side of the pressure ring and connect via splice plate.
4. Check if joint between the clamps is closed tightely by the sealant.
5. Install refrigeration clamp by means of Mounting Kit.