Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country

Group: 1250
Part number 191351
Used for cold-water pipeline systems and refrigeration installations; provides fixation and reduces sound and vibration
First-class sound absorption with soft foam; elastomer part adjusts pipe diameter tolerances and prevents condensation
One size fits multiple pipe dimensions; no sealant needed; suitable for heavy loads

B1 | 420 mm |
b2 | 100 mm |
D | 221 mm |
D2 | 221 mm |
H | 362 mm |
Ma | 1/2" |
Mi1 | M12 |
Mi2 | M16 |
The insulation insert is firmly integrated in the Stabil Clamp. With inserted and welded 3G triple thread nut.
Retaining and clamping bolts are inserted on both sides of the lower part and cannot fall out due to a plastic washer.
Multifaceted connection options via the external thread of the 3G triple thread nut with Adapter AD f/f.
-VZ,perm. | 8,00 kN |
Max. temperature | 110 °C |
Min. temperature | -50 °C |
Thermal Conductivity λ {10°C} | λ = 0,042 W/Mk |
Thermal Conductivity λ {20°C} | λ = 0,043 W/Mk |
Thermal Conductivity λ {30°C} | λ = 0,044 W/Mk |
Thermal Conductivity λ {40°C} | λ = 0,045 W/Mk |
Fire Performance | EL according to DIN EN 13501-1 |
Compressive strength | 0,70 N/mm² |
Insertion Isolation | 25,3 dB(A) |
Insertion Isolation as system test | 26,3 dB(A) |
Bulk Density | 250,00 kg/m³ |
Halogen-free | Yes |
Material base body | steel |
Material insulation body | PUR |
Material connecting element | steel |
Surface | electro galvanized (Fe//Zn) |
Corossion class | C2 |
Certification

| Size [mm] | Tightening torque [Nm] |
|---|---|
| 17 - 22 | 2 |
| 23 - 26 | 2 |
| 27 - 32 | 2 |
| 33 - 38 | 2 |
| 38 - 47 | 3 |
| 48 - 54 | 3 |
| 57 - 62 | 3 |
| 63 - 68 | 3 |
| 70 - 75 | 3 |
| 76 - 81 | 5 |
| 89 - 94 | 5 |
| 107 - 112 | 10 |
| 113 - 117 | 10 |
| 125 - 128 | 10 |
| 133 - 137 | 10 |
| 138 - 142 | 10 |
| 157 - 161 | 10 |
| 168 - 172 | 10 |
| 219 - 327 | 15 |