Certification


Primary element material | steel |
Surface finish | HCP |
Corrosion protection class | C4 |
Type | -VX,perm. | VX,perm. |
PK-4KT F 80 HCP | 10,00 kN | 10,00 kN |
PK-8KT F 80 HCP | 10,00 kN | 10,00 kN |
Type | -MY,perm. | MY,perm. | -MZ,perm. | MZ,perm. |
PK-4KT F 80 HCP | 5,09 kNm | 5,09 kNm | 5,09 kNm | 5,09 kNm |
PK-8KT F 80 HCP | 3,54 kNm | 3,54 kNm | 3,54 kNm | 3,54 kNm |
The specified load values are design loads Rd and include a partial safety factor γM2 = 1.25 (DIN EN 1993-1-8:2025-04, Table 4.1)
A partial safety factor of γG = 1.35 (DIN EN 1990:2021-10, Table A1.2(B)) must be taken into account for permanent loads.
Also available with DualShield for high corrosion protection within C5H environments.
Software
This product is available in the following software.

To be fastened with 2 x 4 FLS F Self Forming Screws. For optimal bending moment, distance between screws to be as far from each other as possible.
Notice:
Self Forming Screw FLS F to be fastened on two sides with a distance of minimum of 100mm (for type 4kt) / 50 mm (for type 8kt) and to be fastened symmetrically. To optimise the bending moment the FLS F should be installed to maintain the pipe weight of the effective flow - i.e. screws are located top and bottom for horizontal cross bars not sideways.
Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country
Info | Type | Weight | Quantity | Part number | |
| PK-4KT F 80 HCP | 2.1 kg/pcs. | 1 pcs. | 111445 | ||
| PK-8KT F 80 HCP | 1.4 kg/pcs. | 1 pcs. | 111446 | ||