Products

Search

High Corrosion Protected Products

Enlarge picture Enlarge picture
For single channels
Enlarge picture Enlarge picture
For double channels

End Support WBD hcp

page as pdf page as pdf

Group: 1856

Application

In combination with a channel, End Support WBD is particularly suitable

  • for setting up structures attached to walls, floors and ceilings and in particular
  • as a base for frame structures made of Sikla channels.
The generous dimensions and the rhomib shape of the mounting plate provide for a high bending moment and safely stabilise lateral loads.

Installation

Normally, two anchors grouped opposite to each other and along the load axis are sufficient. Only in exceptional cases (e.g. high props in frameworks) four anchors are required.

Tighening torque for hexagon bolts ≥ 40 Nm.

For ceiling mounting under high loads (up to 7.0 kN), we recommend the use of at least one fully traversing bolt for connecting the channel to the End Support WBD (for examples see "Installation Guidelines").

Technical Data

Type
Suitable for Sikla
channel
A
[mm]
s
[mm]
B
[mm]
b
[mm]
h
[mm]
C
[mm]
41/21-31 41/21/2.0 - 41/31/2.0 135 6 100 25 11 95
41/41-45 41/41/2.5 135 6 100 25 11 95
41/41-45 D 41/41/2.5 D 210 8 170 25 13 125


Working load for Wall mounting:
See tables on load charts for End Support WBD in chapter "Brackets"
The figures apply on walls if two anchors of the load class as stated are used.

Working load for Ceiling mounting:
The permissible maximum vertical load for ceiling mounting with Holding Bracket amounts to 2.0 kN. Using at least one traversing bolt (class 8.8) 7.0 kN.

Material:
Steel, HCP
Type W
[kg]
Quantity
[pack]
Part
number
41/21-31 0.73 10 198063
41/41-45 0.83 10 198070
41/41-45 D 2.46 5 198100

back to chapter