Application

Anchor for push-through and mounting in M&E services and plant construction in concrete tensile zones.
This anchor combines high admissible loads with little edge and centre distances.
Suitable for attaching pipelines, channels, brackets, etc. in closed room and outside section.

  • No special drill required. Bore dia. = Thread size
  • Simple and quick mounting due to its push-through concept
  • Drive-in hammer zone for preventing any thread damage

Configuration

Supplied with washer and hexagon nut.

Installation

1.
Drill bore hole according to the minimum bore hole depth perpendicularly to the surface.
2.
Remove dirt from the hole.
3.
Drive the anchor into concrete up to its embedment mark.
4.
Immediately resilient after tightening with the torque wrench Tinst indicated in the table below. Advices of the mounting instruction are to be respected!

Technical Data

Type
M8
M10
M12
M16
Perm. load 1) tension C20/25 2) [kN] 2.4 4.3 5.7 11.9
C25/30 2) [kN] 2.6 4.7 6.3 13.1
C30/37 2) [kN] 2.9 5.2 7.0 14.5
C40/50 2) [kN] 3.4 6.0 8.1 16.8
C50/60 2) [kN] 3.7 6.6 8.9 18.5
Perm. load 1) oblique C20/25 2) [kN] 7.4
(5.0)3) 
11.4
(6.5)3) 
17.1 26.9
≥ C25/30 2) [kN] 7.4
(5.5)3) 
11.4
(7.2)3) 
17.1 29.6
Perm. bending moment 1) [Nm] 14.9
(13.7)3) 
29.7
(28)3) 
52.6 133.1
Min. thickness of component hmin ≥ [mm] 100 120 130 160
(3 hef ) Charact. centre distance scr [mm] 138 180 195 255
(1,5 hef ) Charact. edge distance ccr [mm] 69 90 97.5 127.5
Min. centre distance s at/edge distance c ≥ [mm] 40/70 50/75 60/100 60/100
Min. edge distance c at/centre distance s ≥ [mm] 40/80 55/90 60/140 60/180
Effective Anchoring depth hef [mm] 46
(35)3) 
60
(42)3) 
65 85
Nominal diameter of drill d0 [mm] 8 10 12 16
Depth of bore hole h1 ≥ [mm] 60
(55)3) 
75
(65)3) 
90 110
Anchoring torque Tinst [Nm] 20
(15)3) 
35
(30)3) 
50 110
Perm. load tension 4) for fire exposure    
Perm. load R30 perm. F [kN] 1.3 2.3 3.0 6.3
Perm. load R60 perm. F [kN] 1.3 2.3 3.0 6.3
Perm. load R90 perm. F [kN] 1.3 2.3 3.0 6.3
Perm. load R120 perm. F [kN] 1.0 1.8 2.4 5.0


1) Loads for single anchors without influence of edge distances
2) Cracked concrete (option 1)
3) Value in brackets is valid for types marked *.
4) Consider edge and centre distances under fire exposure accord. to approval

The safety factor accord. to ETAG is respected. Values of the mentioned approval are valid and could be seen in the latest issue under www.sikla.com/service/downloads.

Material:
Stainless steel A4/316

Approvals

ETA Approval number: ETA-10/0259
FM Approval for M10, M12, M16
VdS compliant for all sizes
Shock approval issued by the Federal Office for Civil Defence, Bern (Switzerland)



The types marked * are not part of the approvals.

Type Thread
connection
tfix = Max.
effective length
[mm]
Total length
[mm]
W
[kg]
Quantity
[pack]
Part
number
8/5/50 A4* M8 5 50 0.02 100 110551
8/10/75 A4 M8 10 75 0.03 100 110457
8/30/95 A4 M8 30 95 0.04 100 110552
8/50/115 A4 M8 50 115 0.04 100 110458
10/10/60 A4 * M10 10 60 0.05 50 110553
10/10/90 A4 M10 10 90 0.06 50 110459
10/15/95 A4 M10 15 95 0.06 50 110554
10/30/110 A4 M10 30 110 0.07 50 110555
10/50/130 A4 M10 50 130 0.08 50 110460
10/100/180 A4 M10 100 180 0.10 50 110461
12/15/110 A4 M12 15 110 0.10 25 110462
12/20/115 A4 M12 20 115 0.10 25 110556
12/30/125 A4 M12 30 125 0.11 25 110557
12/50/145 A4 M12 50 145 0.13 25 110558
12/85/180 A4 M12 85 180 0.15 25 110559
16/25/145 A4 M16 25 145 0.23 20 110560
16/50/170 A4 M16 50 170 0.27 20 110561