Products

Search

Pressix CC 41 - Assembly System

Enlarge picture Enlarge picture
For single channels
Enlarge picture Enlarge picture
For double channels

End Support WBD

page as pdfpage as pdf

Group: 1356

Application

In combination with a channel, End Support WBD is particularly suitable

  • for setting up support structures attached to walls, floors and ceilings and in particular
  • as a base for frame structures made of Sikla channels.
The generous dimensions and the rhomib shape of the mounting plate provide for a high bending moment and safely stabilise lateral loads.

Installation

Normally, two bolts grouped opposite to each other and along the load axis are sufficient. Only in exceptional cases (e.g. high props in frameworks) four bolts are required.

Minimum torque values for the hexagon bolts of the 41 Holding Brackets are:

Types
Holding Brackets
[pcs]
Bolt for Holding
Bracket
Accessories
Torque
[Nm]
41/21-31 up to 41/41-45 1 M10 pre-assembled 40
41/52 up to 41-75/75 2 M12 pre-assembled 60
41/21 D up to 41/45 D 1 M10 in loose form 40
41/52 D up to 41-75/75 D 1 M12 in loose form 60


For ceiling mounting under high loads (up to 7.0 kN), we recommend the use of at least one fully traversing bolt for connecting the channel to the End Support WBD (for examples see "Installation Guideline").

Technical Data

Type
Suitable for für Sikla
channel
A
[mm]
s
[mm]
B
[mm]
b
[mm]
h
[mm]
C
[mm]
41/21-31 41/21/1.5 - 2.0
41/31/2,0
135 6 100 25 11 95
41/41-45 41/41/2.0 - 2.5
41/45/2.5
135 6 100 25 11 95
41/52 41/52/2.5 170 6 120 25 13 135
41/62 41/62/2.5 170 6 120 25 13 135
41-75/65 41-75/65/3.0 210 8 170 25 13 135
41-75/75 41-75/75/3.0 210 8 170 25 13 135
       
41/21 D 41/21/1.5 - 2.0 D 135 6 100 25 11 125
41/41-45 D 41/41/2.0 - 2.5 D
41/45/2.5 D
210 8 170 25 13 125
41/52 D 41/52/2.5 D 210 8 170 25 13 135
41/62 D 41/62/2.5 D 255 8 205 25 13 135
41-75/65 D 41-75/65/3.0 D 255 8 205 25 13 135
41-75/75 D 41-75/75/3.0 D 255 8 205 25 13 135



Working load for Wall mounting:
See tables on the following pages. The figures apply on walls if two bolts of the load class as stated are used.

Working load for Ceiling Mounting:
The permissible maximum vertical load for ceiling mounting structures fixed by way of at least one traversing bolt (class 8.8) amounts to 7.0 kN

For End Supports WBD for single channels, the following values apply subject to the condition that all included accessories are assembled correctly.

Types
Working load (tension)
for ceiling mounting
[kN]
41/21-31 up to 41/41-45 2.0
41/52 up to 41-75/75 4.0

Material
Steel, cold-formed, electro-galvanised

Load charts:

End Support WBD 41/21-31
End Support WBD 41/41-45
End Support WBD 41/52
End Support WBD 41/62
End Support WBD 41-75/65
End Support WBD 41-75/75

Type For Sikla Channel Holding Brackets
[number of]
W
[kg]
Quantity/
[pack]
Part
number
41/21-31 41/21/2.5 1 0.73 10 177725
41/41-45 41/41/2.5; 41/45/3.0 1 0.83 10 155054
41/52 41/52/3.0 2 1.44 5 177734
41/62 41/62/3.0 2 1.50 5 155063
41-75/65 41-75/65/3.0 2 2.15 5 177743
41-75/75 41-75/75/3.0 2 2.19 5 177752
41/21 D 41/21/2.5 D 1 1.14 5 146469
41/41-45 D 41/41/2.5 D; 41/45/3.0 D 1 2.46 5 106768
41/52 D 41/52/3.0 D 1 2.86 5 177761
41/62 D 41/62/3.0 D 1 4.00 5 155090
41-75/65 D 41-75/65/3.0 D 1 4.18 5 177770
41-75/75 D 41-75/75/3.0 D 1 4.38 5 177779

back to chapter