Group: 1308
Quick-installation element for efficiently mounting pipe clamps and other components to all Sikla Channels of the 41 series. The width is suitable for double channels also.
Pre-assembled.
Insert the Block into the channel; by turning the Holding Bracket by 90° to the right, the Channel Nut locks into the stop position; then tighten nut or other connecting part - the job is done!
Attention:
Minimum screwing depth from the lower edge of the Holding Bracket = 20 mm.
The permissible load is determined by the threaded (grooved) rods used. Also the point carrying capacity of the channel and its torsional moment must not be exceeded.
These values are to be seen in the technical data of the respective products.
| FQ = | Permissible lateral force (applicable also against displacing) |
| FZ = | Permissible tensile force at the Block |
| M = | Tightening moment of the nut or of another connecting component for reaching the lateral force FQ(applicable to all grub screws of Class 4.6 and greater without grooves in the tightening area) |
| Material: | Steel, electro-galvanised |
See the nominal loads for BlockPB 41 in the following table.
| Type | M [Nm] |
FZ [kN] |
FQ [kN] |
W [kg] |
Quantity/ [pack] |
Part number |
|---|---|---|---|---|---|---|
| M8 | 10 | 5.8 | 1.5 | 0.11 | 50 | 160380 |
| M10 | 18 | 9.3 | 2.5 | 0.11 | 50 | 160399 |
| M12 | 32 | 10.0 | 3.0 | 0.13 | 50 | 171287 |