Group: 1382
Refrigeration clamp for the absorption of axial forces.
Especially used for risers or as fixed point clamp. The contraction forces are transferred to the pipe clamp by a pressure ring welded to the perimeter of the pipe. The clamp is anchored to the building structure via an installed anchor bracket.
4 half shells, 2 splice plates, 1 pressure ring as well as bolts and nuts.
Delivery time: 10 working days
| 1. | Weld pressure ring to pipe at location of required anchor point and conserve subsequently. |
| 2. | Apply a thin bead of sealant to the inside adjacent shell faces of the clamp. |
| 3. | Position clamp shells on either side of the pressure ring and connect via splice plate. |
| 4. | Check if joint between the clamps is closed tightely by the sealant. |
| 5. | Install refrigeration clamp by means of Mounting Kit. |
| Insulation: | closed-cell PUR-foam RG 250 kg/m3 |
| Diffusion resistance: | µ = 2500 |
| Thermal conductivity: | λ = 0.040 W/mK (0°C) |
| Fire resistance: | B2 |
| Type [NB] |
Insulation thickness S [mm] |
Max. Load of Fixed Point shear [kN] |
L [mm] |
B [mm] |
W [kg] |
Quantity/ [pack] |
Part number |
|---|---|---|---|---|---|---|---|
| 76.1 | 30 | 2.0 | 171 | 202 | 2.02 | 1 | 190271 |
| 88.9 | 30 | 2.0 | 179 | 206 | 2.28 | 1 | 190289 |
| 108 | 30 | 2.5 | 200 | 220 | 3.48 | 1 | 190298 |
| 114.3 | 40 | 3.0 | 230 | 274 | 4.24 | 1 | 190307 |
| 133 | 40 | 3.5 | 264 | 300 | 4.52 | 1 | 190316 |
| 139.7 | 40 | 5.0 | 264 | 300 | 4.82 | 1 | 190325 |
| 168.3 | 40 | 5.5 | 288 | 328 | 5.62 | 1 | 190343 |
| 219.1 | 60 | 9.5 | 399 | 439 | 16.14 | 1 | 190352 |
| 273 | 60 | 13.0 | 453 | 493 | 17.54 | 1 | 190379 |
| 323.9 | 60 | 14.5 | 504 | 544 | 23.34 | 1 | 190388 |