Group: 1227
For wall, ceiling and floor installation of mounting elements in M&E services.
Permissible anchor values may restrict the application.
| Type | Working load (tension) [kN] | Max. perm. bending moment* [Nm] | Max. lever arm [mm] |
|---|---|---|---|
| Normal M8 | 1.5 | 8.8 | 150 |
| Normal M10/ M10 RL | 1.5 | 17.2 | 200 |
| Normal R 1/2" | 1.5 | 25.0 | 300 |
| Stabil M10 | 3.0 | 17.2 | 200 |
| Stabil M12 | 3.0 | 29.6 | 300 |
| Stabil M16 | 4.5 | 70.3 | 300 |
| Stabil R 1/2" | 4.5 | 95.0 | 350 |
| Stabil R 3/4" | 6.2 | 180.0 | 450 |
| Stabil R 1" | 6.2 | 350.0 | 500 |
| * | Limitation caused by the Mounting Plate or the loading capacity of the grub screw or of the threaded tube. σperm ≤ 160 N/mm2 fperm < 5 mm |
| Material: | Steel, electro-galvanised |
| Type | Dimension L x W x Th [mm] |
Elongated hole d x a [mm] |
Centre distance l [mm] |
W [kg] |
Quantity/ [pack] |
Part number |
|---|---|---|---|---|---|---|
| Normal M8 | 80 x 30 x 3 | 9 x 16 | 54 | 0.05 | 50 | 107501 |
| Normal M10 | 80 x 30 x 3 | 9 x 16 | 54 | 0.06 | 50 | 138361 |
| Normal M10 RL | 80 x 30 x 3 | ø 4.5 | 54 | 0.06 | 50 | 199077 |
| Normal R 1/2" | 80 x 30 x 3 | 9 x 16 | 54 | 0.08 | 50 | 138501 |
| Stabil M10 | 120 x 40 x 4 | 11 x 25 | 80 | 0.14 | 50 | 138343 |
| Stabil M12 | 120 x 40 x 4 | 11 x 25 | 80 | 0.15 | 50 | 107556 |
| Stabil M16 | 120 x 40 x 5 | 11 x 25 | 80 | 0.19 | 50 | 138352 |
| Stabil R 1/2" | 120 x 40 x 5 | 11 x 25 | 80 | 0.20 | 50 | 138529 |
| Stabil R 3/4" | 120 x 40 x 5 | 11 x 25 | 80 | 0.20 | 50 | 138538 |
| Stabil R 1" | 120 x 40 x 5 | 11 x 25 | 80 | 0.22 | 50 | 107592 |