Group: 1401

Application

Hammerset Anchor for non-cracked concrete used for all M&E services. Suitable for fixing pipelines, channels, etc. meeting the respective approval requirements - for damp locations and outdoor constructions the stainless steel version is required.

  • No special drill required
  • Setting tool for distance-controlled forced expansion.
  • Suitable for push-through mounting

Installation

As expansion tool use the respecive expansion cone for drive plug.
The "intelligent" expansion cone facilitates the mounting with bore dia. tolerances.

Technical Data

Permissible load (tensile, shear, oblique) in cracked concrete multiple fixation:
M8
M8 x 40
M10
M12
Permissible load for single plug C20/25-C50/60 [kN] 1.7 2.0 2.0 2.4
Permissible bending moments (Steel 4.6) Mperm [Nm] 6.4 6.4 12.8 22.2
Permissible bending moments (Steel 8.8) Mper [Nm] 17.1 17.1 34.3 60.0
Loads under fire exposure
Permissible load R30 to R90 perm. F [kN] 0.9 0.9 1.5 1.5
Permissible load R120 perm. F [kN] 0.4 0.4 1.0 1.2

Mounting dates in general: M8 M8 x 40 M10 M12 M16
Nominal diameter of drill d0 = [mm] 10 10 12 15 20
Depth of bore hole h0 = [mm] 30 40 40 50 65
Push-through hole in connecting component
df ≤ [mm]
9 9 12 14 18
Length of thread/max. Anchoring depth Lth [mm] 13 20 15 18 23
Minimum anchoring depth Lsdmin [mm] 9 9 11 13 18
Max. tightening torque when mounting Tinst = [Nm] 8 8 15 35 60
Minimum thickness of component hmin [mm] 100 100 120 130 160
Min. centre distance smin [mm] 60 80 100 120 150
Min. edge distance cmin [mm] 95 95 135 165 200

Approval for anchoring in non-cracked concrete: M8* M8 x 40 M10 M12 M16
Perm. tension load C20/25 (Steel 4.6 up to 8.8) [kN] 2.8 3.6 5.1 7.1 10.5
Oblique (Steel 4.6) perm. V ≥ C20/25 [kN] 3.1 3.1 4.1 7.2 13.4
Oblique (Steel 8.8) perm. V ≥ C20/25 [kN] 3.9 3.9 4.1 12.0 18.0
Bending moments (screw 4.6) perm. M [Nm] 6.4 6.4 12.8 22.2 56.8
Bending moments (screw 8.8) perm. M [Nm] 17.1 17.1 34.3 60.0 152.0


* Application for indeterminated static systems

Details on bearing capacities without influence of centre distances or edge distances.
For detailed dimensioning (see report).

Material:
Steel, electro-galvanised, expansion cone is retained preventing accidental falling out

Approvals

For multiple mounting of non-bearing systems:
MKT-Approval ETA-05/0116, for anchorage in non-cracked concrete MKT-Approval ETA-02/0020, Fire protection examination, VdS-conform, FM-Approval ≥ M10

Type Length
[mm]
W
[kg]
Quantity/
[pack]
Part
number
M8 30 0.01 100 125505
M8 x 40 40 0.01 100 153283
M10 40 0.02 50 125514
M12 50 0.04 50 125523
M16 65 0.10 25 112518