Group: 1401
Hammerset Anchor for non-cracked concrete used for all M&E services. Suitable for fixing pipelines, channels, etc. meeting the respective approval requirements - for damp locations and outdoor constructions the stainless steel version is required.
As expansion tool use the respecive expansion cone for drive plug.
The "intelligent" expansion cone facilitates the mounting with bore dia. tolerances.
| Permissible load (tensile, shear, oblique) in cracked concrete multiple fixation: | M8 | M8 x 40 | M10 | M12 |
| Permissible load for single plug C20/25-C50/60 [kN] | 1.7 | 2.0 | 2.0 | 2.4 |
| Permissible bending moments (Steel 4.6) Mperm [Nm] | 6.4 | 6.4 | 12.8 | 22.2 |
| Permissible bending moments (Steel 8.8) Mper [Nm] | 17.1 | 17.1 | 34.3 | 60.0 |
| Loads under fire exposure | | |||
| Permissible load R30 to R90 perm. F [kN] | 0.9 | 0.9 | 1.5 | 1.5 |
| Permissible load R120 perm. F [kN] | 0.4 | 0.4 | 1.0 | 1.2 |
| Mounting dates in general: | M8 | M8 x 40 | M10 | M12 | M16 |
| Nominal diameter of drill d0 = [mm] | 10 | 10 | 12 | 15 | 20 |
| Depth of bore hole h0 = [mm] | 30 | 40 | 40 | 50 | 65 |
| Push-through hole in connecting component df ≤ [mm] | 9 | 9 | 12 | 14 | 18 |
| Length of thread/max. Anchoring depth Lth [mm] | 13 | 20 | 15 | 18 | 23 |
| Minimum anchoring depth Lsdmin [mm] | 9 | 9 | 11 | 13 | 18 |
| Max. tightening torque when mounting Tinst = [Nm] | 8 | 8 | 15 | 35 | 60 |
| Minimum thickness of component hmin [mm] | 100 | 100 | 120 | 130 | 160 |
| Min. centre distance smin [mm] | 60 | 80 | 100 | 120 | 150 |
| Min. edge distance cmin [mm] | 95 | 95 | 135 | 165 | 200 |
| Approval for anchoring in non-cracked concrete: | M8* | M8 x 40 | M10 | M12 | M16 |
| Perm. tension load C20/25 (Steel 4.6 up to 8.8) [kN] | 2.8 | 3.6 | 5.1 | 7.1 | 10.5 |
| Oblique (Steel 4.6) perm. V ≥ C20/25 [kN] | 3.1 | 3.1 | 4.1 | 7.2 | 13.4 |
| Oblique (Steel 8.8) perm. V ≥ C20/25 [kN] | 3.9 | 3.9 | 4.1 | 12.0 | 18.0 |
| Bending moments (screw 4.6) perm. M [Nm] | 6.4 | 6.4 | 12.8 | 22.2 | 56.8 |
| Bending moments (screw 8.8) perm. M [Nm] | 17.1 | 17.1 | 34.3 | 60.0 | 152.0 |
* Application for indeterminated static systems
Details on bearing capacities without influence of centre distances or edge distances.
For detailed dimensioning (see report).
| Material: | Steel, electro-galvanised, expansion cone is retained preventing accidental falling out |
For multiple mounting of non-bearing systems:
MKT-Approval ETA-05/0116, for anchorage in non-cracked concrete MKT-Approval ETA-02/0020, Fire protection examination, VdS-conform, FM-Approval ≥ M10
| Type | Length [mm] |
W [kg] |
Quantity/ [pack] |
Part number |
|---|---|---|---|---|
| M8 | 30 | 0.01 | 100 | 125505 |
| M8 x 40 | 40 | 0.01 | 100 | 153283 |
| M10 | 40 | 0.02 | 50 | 125514 |
| M12 | 50 | 0.04 | 50 | 125523 |
| M16 | 65 | 0.10 | 25 | 112518 |