Products

Search

Anchors and Small Parts

Bolt Anchor AN BZ Plus

page as pdfpage as pdf

Group: 1408

Application

Anchor for push-through mounting in M&E services and plant construction in concrete tensile zones.
Suitable for attaching pipelines, channels, brackets, etc. in closed room - except for damp locations.

  • No special drill required. Bore dia. = Thread size
  • Simple and quick mounting due to its push-through concept.
  • Drive-in hammer zone for preventing any thread damage

Configuration

Supplied with washer and hexagon nut.

Installation

1.
Drill bore hole according to the minimum bore hole depth perpendicularly to the surface.
2.
Remove dirt from hole.
3.
Drive the anchor into concrete up to its embedment mark.
4.
After tightening the anchor with a torque wrench (see torque indicated in the following table), it may be immediately submitted to loading.


Note the instructions in the mounting manual!

Technical Data

Type
M8
M10
M12
M16
Perm. load 1) tension C20/25 2) [kN] 2.4 4.3 5.7 11.9
C25/30 2) [kN] 2.6 4.7 6.3 13.1
C30/37 2) [kN] 2.9 5.2 7.0 14.5
C40/50 2) [kN] 3.4 6.0 8.1 16.8
C50/60 2) [kN] 3.7 6.6 8.9 18.5
Perm. load 1) oblique C20/25 2) [kN] 8.6 12.6 18.0 26.9
≥ C25/30 2) [kN] 8.6 12.6 18.9 29.6
Perm. bending moment 1) [Nm] 13.1 26.9 46.9 119.4
Min. thickness of component dmin ≥ [mm] 100 120 130 170
Charact. centre distance scr [mm] 138 180 195 255
Charact. edge distance ccr [mm] 69 90 97.5 127.5
Min. centre distance s at/edge distance c ≥ [mm] 40/70 45/70 60/100 60/100
Min. centre distance c at/edge distance s ≥ [mm] 40/80 45/90 60/140 60/180
Effective Anchoring depth hv [mm] 46 60 65 85
Nominal diameter of drill d0 [mm] 8 10 12 16
Depth of bore hole t ≥ [mm] 60 75 90 110
Anchoring torque MD [Nm] 20 25 45 90
Perm. load tension 3) for fire exposure    
30 min. N(30) [kN] 1.3 2.2 3.0 6.0
60 min. N(60) [kN] 1.1 1.8 2.8 5.2
90 min. N(90) [kN] 0.8 1.4 2.4 4.4
120 min. N(120) [kN] 0.7 1.2 2.2 4.0


1) Loads for single anchors without influence of edge distances
2) Cracking concrete

Material:
Steel, electro-galvanised

Approvals

ETA-approval number: ETA-03/0017
FM Approval for M10, M12, M16
VdS-conform for all sizes (M8, M10, M12, M16)
Shock approval of the Federal Office for Civil Defence, Bern (Switzerland)

Type Thread
connection
da = Max. eff.
length [mm]
Total length
[mm]
W
[kg]
Quantity/
[pack]
Part
number
8/10 M8 10 75 0.03 100 166526
8/30 M8 30 95 0.04 100 166535
10/10 M10 10 90 0.06 50 166544
10/30 M10 30 110 0.07 50 166553
10/50 M10 50 130 0.08 50 166562
12/15 M12 15 110 0.10 25 166571
12/30 M12 30 125 0.11 25 166580
12/50 M12 50 145 0.12 25 166599
12/105 M12 105 200 0.18 25 166605
12/160 M12 160 255 0.23 20 166614
16/25 M16 25 145 0.23 20 166623
16/50 M16 50 170 0.26 20 166632
16/100 M16 100 220 0.35 10 166641

back to chapter